Plenum, Riser or CMX? Understanding Cable Jacket Ratings

What CMP, CMR, CM and CMX mean, where each is allowed, and which ratings can substitute for others.

Why the jacket matters

Communications cable is fire-rated based on where it is installed. The rating printed on the jacket tells an inspector whether the cable is allowed in that space.

The common ratings

RatingNameWhere it is typically used
CMPPlenumAir-handling spaces such as drop ceilings and raised floors used for return air
CMRRiserVertical runs between floors in shafts and risers
CMGeneral purposeHorizontal runs that are not in plenum or riser spaces
CMXLimited useLimited-use applications such as some residential runs

Substitution rules of thumb

  • A higher rating can generally replace a lower one: CMP can be used where CMR, CM or CMX is called for, and CMR can replace CM or CMX.
  • A lower rating cannot replace a higher one — riser cable is not allowed in a plenum space.
  • Plenum cable costs more, so use it where it is required rather than everywhere by default.
  • Always confirm with the project specs and your local authority having jurisdiction (AHJ).

General guidance only — always follow project specifications, manufacturer instructions and local code.